title: The Importance of Measuring Differential Pressure and Particles in Anterooms
description: Inhaling airborne particles can put both critical patients and healthcare staff at risk. Monitoring and controlling these particles is necessary for maintaining safety in a hospital.
image: https://www.setra.com/hubfs/staying-ahead-5x8.gif
---

**

**

**

- Website Pages
- Products

[![Setra Systems Logo](https://www.setra.com/hubfs/setra-logo.svg "Setra Systems Logo")](https://www.setra.com/)

![drop-down-pressure](https://www.setra.com/hs-fs/hubfs/angle-arrow-pointing-to-right.png?width=15&name=angle-arrow-pointing-to-right.png)

**[Pressure Sensors](https://www.setra.com/product/pressure)**

[Differential Pressure Sensors](https://www.setra.com/product/pressure/differential)

[Absolute Pressure Sensors](https://www.setra.com/product/pressure/absolute)

[Barometric Pressure Sensors](https://www.setra.com/product/pressure/barometric)

[Compound Pressure Sensors](https://www.setra.com/product/pressure/compound)

[Gauge Pressure Sensors](https://www.setra.com/product/pressure/gauge)

[Submersible Pressure Sensors](https://www.setra.com/product/pressure/submersible)

[Vacuum Pressure Sensors](https://www.setra.com/product/pressure/vacuum)

[UHP Pressure Sensors](https://www.setra.com/product/pressure/uhp)

**[Room Pressure Monitors](https://www.setra.com/product/room-pressure-monitors)**

**[Pressure Calibrator](https://www.setra.com/product/calibration/microcal-pressure-calibrator)**

**[Setra CEMS™ Software](https://www.setra.com/cems)**

**[Power Meters & Accessories](https://www.setra.com/product/power-meters)**

**[Particle Counters](https://www.setra.com/product/particle-counters)**

**[Wireless Solution Systems](https://www.setra.com/wireless)**

**[Humidity/Temp Sensors](https://www.setra.com/product/humidity)**

**[Dolan-Jenner Fiber Optics](https://dolan-jenner.com)**

![drop-down-pressure](https://www.setra.com/hs-fs/hubfs/angle-arrow-pointing-to-right.png?width=15&name=angle-arrow-pointing-to-right.png)

**[Building Automation](https://www.setra.com/building-automation)**

[Calibration](https://www.setra.com/building-automation/calibration-equipment)

[HVAC/R OEM](https://www.setra.com/building-automation/hvac-r-oem-applications)

[HVAC/R](https://www.setra.com/building-automation/hvac-applications)

**[Cleanrooms](https://www.setra.com/critical-environments)**

**[Healthcare](https://www.setra.com/critical-environments/healthcare)**

![drop-down-pressure](https://www.setra.com/hs-fs/hubfs/angle-arrow-pointing-to-right.png?width=15&name=angle-arrow-pointing-to-right.png)

**[General Industrial](https://www.setra.com/industrial)**

[Alternative Fuels](https://www.setra.com/general-industrial/vacuum-pressure-in-alternative-fuels)

[Barometric](https://www.setra.com/general-industrial/barometric-pressure-measurement-tools)

[Data Centers](https://www.setra.com/applications/data-centers/pressure-sensors)

[General Industrial OEM](https://www.setra.com/quality-approved-general-industrial-oem-solutions-setra-systems)

[HVAC/R OEM](https://www.setra.com/building-automation/hvac-r-oem-applications)

[Medical](https://www.setra.com/applications/medical-devices/pressure-sensors)

[Off-Highway Vehicles](https://www.setra.com/general-industrial/pressure-transducers-for-off-highway-vehicles)

[Oil & Gas](https://www.setra.com/general-industrial/oil-and-gas-pressure-measurement)

[Process / MFG Tank Level](https://www.setra.com/general-industrial/liquid-level-sensors)

[Test & Measurement](https://www.setra.com/general-industrial/pressure-test-and-measurement)

[Water & Wastewater](https://www.setra.com/general-industrial/liquid-level-sensors-for-water-processing)

**[Semiconductor Manufacturing](https://www.setra.com/semiconductor-manufacturing-pressure-measurement)**

**[Data Centers](https://www.setra.com/applications/data-centers)**

**[Energy Management](https://www.setra.com/energy-management)**

**[Fiber Optics](https://www.setra.com/fiber-optic-illuminators)**

**[Scales](https://www.setra.com/counting-scales-and-laboratory-balances)**

[![setra-nav-logo.png](https://www.setra.com/hs-fs/hubfs/setra-nav-logo.png?width=133&name=setra-nav-logo.png "setra-nav-logo.png")](https://www.setra.com/)

![Menu](https://www.setra.com/hs-fs/hubfs/moble-icon.jpg?width=30&name=moble-icon.jpg)

×

[Home](https://www.setra.com)

Markets >

[Healthcare](https://www.setra.com/critical-environments/healthcare) [Building Automation](https://www.setra.com/building-automation) [Cleanrooms](https://www.setra.com/critical-environments) [General Industrial](https://www.setra.com/industrial) [Semiconductor Manufacturing](https://www.setra.com/semiconductor-manufacturing-pressure-measurement) [Data Centers](https://www.setra.com/applications/data-centers?hsLang=en) [Energy Management](https://www.setra.com/energy-management) [Fiber Optics](https://www.setra.com/fiber-optic-illuminators) [Scales](https://www.setra.com/counting-scales-and-laboratory-balances)

Products >

[Pressure Sensors](https://www.setra.com/product/pressure) [Room Pressure Monitors](https://www.setra.com/product/room-pressure-monitors) [Particle Counters](https://www.setra.com/product/particle-counters) [Setra CEMS™ Software](https://www.setra.com/cems) [Power Meter & Accessories](https://www.setra.com/product/power-meters) [Pressure Calibrator](https://www.setra.com/product/calibration/microcal-pressure-calibrator) [Wireless Solutions Systems](https://www.setra.com/wireless) [Humidity/Temp Sensors](https://www.setra.com/product/humidity) [Dolan-Jener](https://dolan-jenner.com/) 

[OEM Solutions](https://www.setra.com/custom-solutions)

Resources >

[Blog](https://www.setra.com/blog) [Videos](https://www.setra.com/video-resources) [FAQs](https://article.setra.com/) [Compliance](https://article.setra.com/compliance-documents) [Supplier](https://www.setra.com/support/supplier) [Current Customers](https://www.setra.com/support/customer) 

[Order Online](https://ecatalog.setra.com)

Returns >

[Services & Calibration](https://www.setra.com/support/service) [New and Unused for Credit](https://www.setra.com/product-return) 

[Contact Us](https://www.setra.com/help-center)

# The Importance of Measuring Differential Pressure and Particles in Anterooms

#### by [Meghan Kelley](https://www.setra.com/blog/author/meghan-kelley)

- [Tweet](https://twitter.com/share)

Inhaling airborne particles can put both critical patients and healthcare staff at risk for detrimental health issues. Controlling these particles is necessary for protecting both staff and occupants of nearby rooms from exposure to infectious particles. To maintain safety in a hospital, it is crucial to monitor both differential pressure and particle counts in anterooms.

[Isolation rooms](https://www.setra.com/blog/what-are-airborne-infection-isolation-rooms) are a specialized application of a hospital's HVAC system to prevent infectious airborne particles from escaping into public areas. Some of the control of these particles relies on ventilation, including both air change rates and differential pressure. Although a high air change rate can be useful, it is not a guarantee for removal of contagious particles from the air.

## Why Monitor Differential Pressure?

Differential pressure between an isolation room and an anteroom is a better technique to limit particle transmission. Regardless of how it is pressurized in relation to the hallway, an anteroom is designed to be a buffer and guarantee negative pressure in the patient room.

To prevent contaminants from escaping the room, it is important to have a differential pressure ![Setra Hotwire Replacement Kit](https://www.setra.com/hs-fs/hubfs/retrofit_hot-wire_kit.jpg?width=206&name=retrofit_hot-wire_kit.jpg)transducer with high accuracy that does not degrade over time. Common [hotwire anemometers](https://www.setra.com/blog/why-you-should-replace-your-hot-wire-anemometer) can become clogged with dust, resulting in significantly reduced performance in mere weeks. Replacing a hotwire anemometer with a dead-ended differential pressure transducer like the sensor inside Setra's [Hotwire Replacement Kit](https://www.setra.com/product/room-pressure-monitoring/hot-wire-replacement-kit) eliminates costly maintenance and increases the reliability of pressure readings.

The simplest way to monitor and control a differential pressure transducer is with a room pressure monitor. An environmental monitor such as Setra [FLEX](https://www.setra.com/setra-flex) makes the management of differential pressure transducers visual and intuitive.

## Why Monitor Particle Counts?

[Non-viable particles](https://www.setra.com/blog/what-can-a-non-viable-particle-counter-do-that-viable-air-sampling-cannot) can have adverse effects on patient health and can indicate the presence of dangerous microbes. Particle counters within isolation rooms and anterooms represent an effective tool to help eliminate the spread of infectious particles throughout a hospital. When used in conjunction with environmental monitors, the risk to patient health can be drastically reduced. A particle counter with programmable alarms can indicate potential issues within an otherwise sterile environment.

Particle counters typically detect and measure non-viable contaminants such as dust, mold spores,[![staying ahead with particle counting](https://www.setra.com/hs-fs/hubfs/staying-ahead-5x8.gif?width=441&name=staying-ahead-5x8.gif)](https://www.setra.com/product/particle-counting/5000-series) debris, and volatile organic compounds (VOCs). Although particle counters focus on non-viable particles, said particles are often vehicles for viable contaminants. A spike in non-viable particles is often an indicator of a spike in infectious particles. Setra's [SPC5000](https://www.setra.com/product/particle-counting/5000-series) particle counter is a perfect tool to help maintain cleanliness and isolation in these critical environments. 

 Topics: [Room Pressure Monitoring](https://www.setra.com/blog/topic/room-pressure-monitoring), [Critical Environments](https://www.setra.com/blog/topic/critical-environments), [pressure transducers](https://www.setra.com/blog/topic/pressure-transducers), [Particle Counting](https://www.setra.com/blog/topic/particle-counting)

### Recent Posts

### Posts by Topic

- [Critical Environments (184)](https://www.setra.com/blog/topic/critical-environments)
- [HVAC/R (180)](https://www.setra.com/blog/topic/hvac-r)
- [General Industrial (153)](https://www.setra.com/blog/topic/general-industrial)
- [Building Automation (135)](https://www.setra.com/blog/topic/building-automation)
- [General Industrial OEM (92)](https://www.setra.com/blog/topic/general-industrial-oem)
- [Energy Management (85)](https://www.setra.com/blog/topic/energy-management)
- [Test and Measurement (66)](https://www.setra.com/blog/topic/test-and-measurement)
- [HVAC/R OEM (60)](https://www.setra.com/blog/topic/hvac-r-oem)
- [Barometric (44)](https://www.setra.com/blog/topic/barometric)
- [Alternative Fuels (42)](https://www.setra.com/blog/topic/alternative-fuels)
- [Medical (41)](https://www.setra.com/blog/topic/medical)
- [Process/Mfg Tank Level (40)](https://www.setra.com/blog/topic/process-mfg-tank-level)
- [Water and Wastewater (39)](https://www.setra.com/blog/topic/water-and-wastewater)
- [OHV (38)](https://www.setra.com/blog/topic/ohv)
- [Oil and Gas (35)](https://www.setra.com/blog/topic/oil-and-gas)
- [Industrial Vacuum (29)](https://www.setra.com/blog/topic/industrial-vacuum)
- [Calibration (25)](https://www.setra.com/blog/topic/calibration)
- [Semiconductor (25)](https://www.setra.com/blog/topic/semiconductor)
- [Particle Counting (20)](https://www.setra.com/blog/topic/particle-counting)
- [Cleanroom Monitoring (18)](https://www.setra.com/blog/topic/cleanroom-monitoring)
- [Room Pressure Monitoring (17)](https://www.setra.com/blog/topic/room-pressure-monitoring)
- [Trade Show (12)](https://www.setra.com/blog/topic/trade-show)
- [cleanroom environment (12)](https://www.setra.com/blog/topic/cleanroom-environment)
- [Environmental Monitoring (11)](https://www.setra.com/blog/topic/environmental-monitoring)
- [Power Meters (11)](https://www.setra.com/blog/topic/power-meters)
- [Scales (11)](https://www.setra.com/blog/topic/scales)
- [Healthcare (10)](https://www.setra.com/blog/topic/healthcare)
- [Power Monitoring (10)](https://www.setra.com/blog/topic/power-monitoring)
- [Software (9)](https://www.setra.com/blog/topic/software)
- [cleanroom monitoring systems (9)](https://www.setra.com/blog/topic/cleanroom-monitoring-systems)
- [Case Study (8)](https://www.setra.com/blog/topic/case-study)
- [critical environment technologies (8)](https://www.setra.com/blog/topic/critical-environment-technologies)
- [data centers (8)](https://www.setra.com/blog/topic/data-centers)
- [Humidity (7)](https://www.setra.com/blog/topic/humidity)
- [particle counter (6)](https://www.setra.com/blog/topic/particle-counter)
- [pressure transducers (6)](https://www.setra.com/blog/topic/pressure-transducers)
- [LITE room pressure monitor (5)](https://www.setra.com/blog/topic/lite-room-pressure-monitor)
- [hardware and software cleanroom monitoring systems (5)](https://www.setra.com/blog/topic/hardware-and-software-cleanroom-monitoring-systems)
- [setra lite (5)](https://www.setra.com/blog/topic/setra-lite)
- [Compliance (4)](https://www.setra.com/blog/topic/compliance)
- [Video (3)](https://www.setra.com/blog/topic/video)
- [hospital spaces (3)](https://www.setra.com/blog/topic/hospital-spaces)
- [FAQ & Troubleshooting (2)](https://www.setra.com/blog/topic/faq-troubleshooting)
- [Monitoring Compounding Pharmacies (2)](https://www.setra.com/blog/topic/monitoring-compounding-pharmacies)
- [Semiconductor Manufacturing (2)](https://www.setra.com/blog/topic/semiconductor-manufacturing)
- [agencies that monitor pharmacies (2)](https://www.setra.com/blog/topic/agencies-that-monitor-pharmacies)
- [energy (2)](https://www.setra.com/blog/topic/energy)
- [hvac (2)](https://www.setra.com/blog/topic/hvac)
- [laboratories (2)](https://www.setra.com/blog/topic/laboratories)
- [monitor compound pharmacy (2)](https://www.setra.com/blog/topic/monitor-compound-pharmacy)
- [protected environment (2)](https://www.setra.com/blog/topic/protected-environment)
- [regulatory compliance (2)](https://www.setra.com/blog/topic/regulatory-compliance)
- [setra lite features (2)](https://www.setra.com/blog/topic/setra-lite-features)
- [usp 797 (2)](https://www.setra.com/blog/topic/usp-797)
- [Application Note (1)](https://www.setra.com/blog/topic/application-note)
- [Current Sensors and Transducers (1)](https://www.setra.com/blog/topic/current-sensors-and-transducers)
- [Current Transformers (1)](https://www.setra.com/blog/topic/current-transformers)
- [Lithium-Ion Battery (1)](https://www.setra.com/blog/topic/lithium-ion-battery)
- [Pressure (1)](https://www.setra.com/blog/topic/pressure)
- [aerospace cleanrooms (1)](https://www.setra.com/blog/topic/aerospace-cleanrooms)
- [cems (1)](https://www.setra.com/blog/topic/cems)
- [digital transformation (1)](https://www.setra.com/blog/topic/digital-transformation)
- [ipv6 multicast (1)](https://www.setra.com/blog/topic/ipv6-multicast)
- [ipv6 multicast address (1)](https://www.setra.com/blog/topic/ipv6-multicast-address)
- [ipv6 multicast address range (1)](https://www.setra.com/blog/topic/ipv6-multicast-address-range)
- [isolation room pressure monitoring (1)](https://www.setra.com/blog/topic/isolation-room-pressure-monitoring)
- [multicast address ipv6 (1)](https://www.setra.com/blog/topic/multicast-address-ipv6)
- [multicast ipv6 (1)](https://www.setra.com/blog/topic/multicast-ipv6)
- [operating room (1)](https://www.setra.com/blog/topic/operating-room)
- [pharma 4.0 (1)](https://www.setra.com/blog/topic/pharma-4-0)
- [pressure sensor (1)](https://www.setra.com/blog/topic/pressure-sensor)
- [pressure transducer companies (1)](https://www.setra.com/blog/topic/pressure-transducer-companies)
- [semi conductor (1)](https://www.setra.com/blog/topic/semi-conductor)
- [sensors and transducers (1)](https://www.setra.com/blog/topic/sensors-and-transducers)
- [setra pressure transducers (1)](https://www.setra.com/blog/topic/setra-pressure-transducers)
- [submetering (1)](https://www.setra.com/blog/topic/submetering)
- [sustainability (1)](https://www.setra.com/blog/topic/sustainability)
- [temperature monitor (1)](https://www.setra.com/blog/topic/temperature-monitor)
- [temperature monitoring for pharmacies (1)](https://www.setra.com/blog/topic/temperature-monitoring-for-pharmacies)
- [transducers (1)](https://www.setra.com/blog/topic/transducers)
- [usp 800 (1)](https://www.setra.com/blog/topic/usp-800)
- [water (1)](https://www.setra.com/blog/topic/water)
- [what does hvac stand for (1)](https://www.setra.com/blog/topic/what-does-hvac-stand-for)
- [what is a transducer (1)](https://www.setra.com/blog/topic/what-is-a-transducer)
- [what is hvac (1)](https://www.setra.com/blog/topic/what-is-hvac)

[see all](https://www.setra.com/blog/the-importance-of-measuring-differential-pressure-and-particles-in-anterooms#)

[![HVAC Catalog Cover Image 1](https://www.setra.com/hs-fs/hubfs/HVAC%20Catalog%20Cover%20Image%201.png?width=160&name=HVAC%20Catalog%20Cover%20Image%201.png "HVAC Catalog Cover Image 1")](http://setrasystems.uberflip.com/setra-systems/hvac-catalog-feb-2017)

 

**HVAC Catalog**

 

This comprehensive HVAC Product Catalog is now available online. [Download the PDF now.](http://setrasystems.uberflip.com/setra-systems/hvac-catalog-feb-2017)

 

- [**](https://www.facebook.com/SetraSystems)
- [**](https://twitter.com/setrasystems)
- [**](https://www.youtube.com/user/SetraSystems)
- [**](https://www.linkedin.com/company/setra-systems)
- [**](https://www.instagram.com/setrasystemsinc/)

[Service & Calibration](https://www.setra.com/support/service) | [Products](https://www.setra.com/products) | [Service/RMA](https://www.setra.com/support/service) | [Supplier](https://www.setra.com/support/supplier) | [Customer](https://www.setra.com/support/customer) | [Contact Us](https://www.setra.com/contact-us) | [FAQs](https://faq.setra.com) | [About](https://www.setra.com/about) | [Careers](https://careers.fortive.com/gems-setra/) | [Request Quote](https://www.setra.com/request-a-quote) | [Blog](https://www.setra.com/blog)

 Cookie Settings

159 Swanson Road Boxborough, MA 01719 | [orders@setra.com](mailto:orders@setra.com)

[+1 (978) 263-1400

](tel:+19782631400)

Copyright © 2026 Setra Systems. All Rights Reserved. | [Terms & Conditions](https://www.setra.com/terms-and-conditions) | [Privacy Notice](https://www.setra.com/privacy-policy) | [ISO 9001:2015 Certified | ](https://www.setra.com/hubfs/ISO%20Setra%20LLC%202025.pdf)[Prop 65](https://www.setra.com/prop65) | [Patents](https://www.setra.com/patents) | [Cookies](https://www.setra.com/cookies)

[![Setra Systems Logo](https://www.setra.com/hs-fs/hubfs/setra-systems-logo_white-1.png?width=100&name=setra-systems-logo_white-1.png)](https://www.setra.com/)[![Ralliant logo](https://www.setra.com/hs-fs/hubfs/Ralliant_Logo_SingleColor_White_RGB.png?width=125&name=Ralliant_Logo_SingleColor_White_RGB.png "Setra Systems is a Ralliant Company")](https://www.ralliant.com/)