Explosion-Proof/Intrinsically Safe

This application note defines some of the terms associated with use of transducers and electrical equipment in areas which are defined as hazardous by national rating agencies. It also outlines Setra products which have Factory Mutual approvals for use in hazardous areas.

Explosion-Proof

"Explosion-proof" products are capable of containing an explosion. The term "explosion-proof" does not indicate that the product is capable of withstanding an external explosion, but only of withstanding an internal explosion without allowing flames or hot gases to escape from the transducer housing to trigger an explosion in the surrounding atmosphere.

The "explosion-proof" term is assigned to those products which are certified by the national rating agencies such as Underwriters Laboratories and Factory Mutual Research after meeting their specifications and passing their tests. Unless certified by one of these agencies, the product does not meet the "explosion-proof" requirements of the National Electrical Code.

Intrinsically Safe

"Intrinsically safe" products receive their classification because their electrical power usage is below the level of power required to set off an explosion within a given hazardous area. In addition, "intrinsically safe'" products are incapable of storing large amounts of energy which might spark an explosion when discharged.

Hazardous Areas

Both national rating agencies, as well as the American National Standards Institute adhere to the same definitions of what contributes a hazardous area. These areas are defined as Class I (combustible gas and liquids), Class II (combustible dust), and Class III (combustible fibers). Class I is subdivided into groups A (acetylene), B (Hydrogen and butadiene), C (diethyl ether, ethylene, isoprene, and UDMH), and D (acetone, gasoline, lacquer solvent, styrene, propane, and natural gas). Class II is divided into Groups E (metal dust), F (carbon black, coal, and coke), and G (flour, starch, and grain dusts).

All classes include two divisions. Division I covers electrical equipment directly exposed in an explosion atmosphere of the material of a specific group. Division II covers electrical equipment in an explosive atmosphere only when accident or fallout occurs, or in a properly vented direct exposure.

Qualification for a rating automatically qualifies the equipment for a lower class and group. For example: Class I equipment can be used in Class II and Class III applications with no restrictions.

An "explosion-proof" rating is given only to a single piece of equipment for a specific class, division, and group. Equipment installation is the sole responsibility of the end user, and the National Electrical Code clearly defines the requirements of this installation. For example, a piece of equipment can carry a Class I rating and qualify only for a Class II rating after installation and inspection if the installation is not up to the original rating requirements. The National Electrical Code allows no modification of the rated equipment.

A single piece of equipment, a system, or parts of a system can receive an "intrinsically safe" rating for a class, group, and division. The rating agencies usually test the equipment as a system, and all parts of the system receive the highest class and group reached by the system regardless of any previous "explosion-proof" rating. The entire system also receives a collective rating, which will generally be that of the lowest rated piece within the system. If the system is not modified by the end user, it retains the rating. The end user must install the equipment as supplied, and installation procedures are not specified by the National Electrical Code.

Reference: National Electrical Code of the American National Standards Institute

Setra products for use in hazardous areas

Setra pressure transducer and transmitter Models 204, C204, 205-2, 280E and C280E, when factory installed in an "explosion proof enclosure", are Factory Mutual approved explosion proof for:

Class I, Division 1 & 2, Group A, B, C, D
Class II, Division 1 & 2, Group E, F, G
Class III, Division 1 & 2
Nema 4 weatherproof

Setra pressure transducers Models 204, 205-2, 228-1 and 239 are available in an "intrinsically safe" design (optional) and are Factory Mutual approved for:

Class I, Division 1 & 2, Group A, B, C, D
Class II, Division 1 & 2, Group E, F, G
Class III, Division 1 & 2

   
top of page  

|PREVIOUS| |INDEX| |NEXT|

|Division Profile| |Products| |Installation Instructions| |Technology|
|Application Notes| |News Releases| |Articles| |Trade Shows| |Sales Offices|

|Site Map| |About Us| |Contact Setra| |Employment|

|Home Page|

   
  159 Swanson Road, Boxborough, MA 01719-1304
Tel (978) 263-1400 · Toll Free (800) 257-3872
     
   

©1998 Setra Systems, Inc. All rights reserved. All names and logos are trademarks. All other names, logos, and trademarks are property of their respective owners.

Web site design by DreamLight Incorporated: DreamLight.com