Skip to main content
Technology & Functionality

Vacuum Pressure: What It Is & How to Measure

The term vacuum is often misunderstood. Consequently, it is commonly misapplied when discussing pressure measurements and choosing pressure transducers. Pressure is the exertion of force upon an object. However, pressure can be measured in many different ways, depending on the applications.


Vacuum Pressure
By definition, vacuum is a space that is partially exhausted (as to the highest degree possible) by artificial means (such as an air pump). This definition is referring to a high or hard vacuum. Figure 1 illustrates that relationship of absolute and gauge pressure with 0 PSIA equal to a high or hard vacuum.
Figure 1:
Vacuum Measurements Range Setra





Gauge Pressure


Gauge pressure is pressure measured relative to ambient atmospheric pressure (approximately 14.7 PSIA). It is referred to as pounds per square inch (gauge) or PSIG. The electrical output of a gauge pressure transducer is 0 VDC at 0 PSIG (14.7 PSIA) and full scale output (typically 5 VDC) at full scale pressure (in PSIG).




Absolute Pressure


Absolute pressure is measured relative to high vacuum (0 PSIA). It is referred to as pounds per square inch (absolute) or PSIA. The electrical output of an absolute pressure transducer is 0 VDC at 0 PSIA and full scale output (typically 5 VDC) at full scale pressure (in PSIA).


Vacuum can refer to any pressure between 0 PSIA and 14.7 PSIA and consequently must be further defined. For applications concerned with measuring vacuum pressures over this full range, two different approaches are often taken.



Figure 2:
Relationship of absolute and vacuum pressures




Vacuum pressure is measured relative to ambient atmospheric pressure. It is referred to as pounds per square inch (vacuum) or PSIV. The electrical output of a vacuum pressure transducer is 0 VDC at 0 PSIV (14.7 PSIA) and full scale output (typically 5 VDC) at full scale vacuum, 14.7 (0 PSIA).


The vacuum pressure transducer gives an increased positive voltage output proportional to decreasing pressure (increasing vacuum). The absolute pressure transducer gives an increased positive voltage output proportional to increasing pressure (decreasing vacuum).


Example:


Vacuum Transducer
Range: 0 to 14.7 PSIV
Output: 0 to 5 VDC


Absolute Transducer
Range: 0 to 14.7 PSIA
Output: 0 to 5 VDC




Differential Pressure


Vacuum also is often referred to as negative pressure (or soft vacuum). This occurs when the application requires monitoring both decreases in pressure below atmospheric pressure and increases in pressure above atmospheric bidirectional differential pressure.



Figure 3:
Relationship between differential and absolute pressure




Here differential pressure is pressure measured relative to a reference pressure. It is referred to as pounds per square inch (differential) or PSID. If the reference pressure is one atmosphere the differential pressure range is equal to gauge pressure range. The electrical output of a bidirectional differential pressure transducer is typically 0 VDC at one atmosphere with increased positive voltage output proportional to increased positive pressure and increased negative voltage output proportional to increased negative pressure.


Example:


Bidirectional Differential Pressure Transducer
Range: 0 to ±5 PSID
Output: 0 to ±2.4 VDC


Bidirectional differential pressure transducers are used for soft or low vacuum measurements (typically greater than 5 PSIA) while low absolute pressure transducers are used for hard or high vacuum measurements (typically less than 5 PSIA).


Figure 4 illustrates soft and hard vacuums.


Figure 4:
Soft and Hard Vacuums Diagram








Setra's Vacuum Sensors


Setra's vacuum pressure transducers are built with capacitive sensing technology and are used in a wide variety of applications. Accurate, reliable, and stable, Setra's Model 206, 209, and 210 have been successfully integrated into applications from injection molding to semiconductor manufacturing. The AXD is the latest addition to this product family and is intended as a robust solution for the most demanding applications.


For more information, take a look at our INDUSTRIAL PRESSURE SENSOR CATALOG