If a button is greyed out (disabled) and says that no device is connected, return to
the communications tab and establish a connection with the meter, then try again.
Register | Modbus | Detailed Description |
Net True Energy LSW | 44001 | System Total Net True Energy LSW (kWh) |
Net True Energy MSW | 44002 | System Total Net True Energy MSW (kWh) |
Total True Power | 44003 | System Total True Power (kW) |
Peak Demand | 44004 | Max Average power window (KW) |
Present Demand | 44005 | Average power (KW) (most recent window) |
Maximum Instantaneous kW | 44006 | System Maximum Instantaneous kW (Highest 500mS kW) |
Minimum Instantaneous kW | 44007 | System Minimum Instantaneous kW (Lowest 500mS kW) |
Net Reactive Energy LSW | 44008 | System Total Net Reactive Energy LSW (kVARh) |
Net Reactive Energy MSW | 44009 | System Total Net Reactive Energy MSW (kVARh) |
Total Reactive Power | 44010 | System Total Reactive Power (kVAR) |
Total Apparent Energy LSW | 44011 | System Total Apparent Energy LSW (kVAh) |
Total Apparent Energy MSW | 44012 | System Total Apparent Energy MSW (kVAh) |
Total Apparent Power | 44013 | System Total Apparent Power (kVA) |
Total Displacement Power Factor | 44014 | System Total Power Factor (PF) |
Total Apparent Power Factor | 44015 | System Total Power Factor (PF) |
Total Current | 44016 | Total current in all phases. |
Voltage Line - Line | 44017 | Voltage Line to line (Volts) Average. |
Voltage Line - Neutral | 44018 | Voltage Line to neutral (volts) Average. |
Voltage Phase A - B | 44019 | Individual Phase to Phase Voltages |
Voltage Phase B - C | 44020 | |
Voltage Phase C - A | 44021 | |
Line Frequency | 44022 | Line Frequency (Hz) |
True Energy Phase A LSW | 44023 | Individual Phase True Energy LSW (kWh) |
True Energy Phase A MSW | 44024 | Individual Phase True Energy MSW (kWh) |
True Energy Phase B LSW | 44025 | |
True Energy Phase B MSW | 44026 | |
True Energy Phase C LSW | 44027 | |
True Energy Phase C MSW | 44028 | |
True Power Phase A | 44029 | Individual Phase True Powers (kW) |
True Power Phase B | 44030 | |
True Power Phase C | 44031 | |
React Energy Phase A LSW | 44032 | Individual Phase Reactive Energy LSW (kVARh) |
React Energy Phase A MSW | 44033 | Individual Phase Reactive Energy MSW (kVARh) |
React Energy Phase B LSW | 44034 | |
React Energy Phase B MSW | 44035 | |
React Energy Phase C LSW | 44036 | |
React Energy Phase C MSW | 44037 | |
React Power Phase A | 44038 | Individual Phase Reactive Powers (kVAR) |
React Power Phase B | 44039 | |
React Power Phase C | 44040 | |
Apparent Energy Phase A LSW | 44041 | Individual Phase Apparent Energy LSW (kVAh) |
Apparent Energy Phase A MSW | 44042 | Individual Phase Apparent Energy MSW (kVAh) |
Apparent Energy Phase B LSW | 44043 | |
Apparent Energy Phase B MSW | 44044 | |
Apparent Energy Phase C LSW | 44045 | |
Apparent Energy Phase C MSW | 44046 | |
Apparent Power Phase A | 44047 | Individual Phase Apparent Powers (kVA) |
Apparent Power Phase B | 44048 | |
Apparent Power Phase C | 44049 | |
dPF Phase A | 44050 | Individual Phase displacement Power Factor (PF) |
dPF Phase B | 44051 | |
dPF Phase C | 44052 | |
aPF Phase A | 44053 | Individual Phase apparent Power Factors (PF) |
aPF Phase B | 44054 | |
aPF Phase C | 44055 | |
Current Phase A | 44056 | Individual Phase Currents (A) |
Current Phase B | 44057 | |
Current Phase C | 44058 | |
Voltage Phase A_N | 44059 | Individual Phase to Neutral Voltages (V) |
Voltage Phase B_N | 44060 | |
Voltage Phase C_N | 44061 | |
Time Since Reset LSW | 44062 | Seconds since KWH register was reset. LSW |
Time Since Reset HSW | 44063 | Seconds since KWH register was reset. MSW |
Data Scalar | 44064 | See Table 1 |
Volts Scalar | 44065 | For use with step-down transformer (not used 6-2007) |
Amps Scalar | 44066 | For use with primary CTs (not used 6/2007) |
Demand Window Size | 44067 | In Minutes (1 to 60) |
CT Value | 44068 | In Amps X10 |
Firmware Major Rev. Number | 44069 | |
Firmware Minor Rev. Number | 44070 | |