Model 528
High Temperature
Pressure Transducer
|
|
Applications
- Off-Highway
- Natural Gas Equipment
- Power Plants
- Semiconductor Processing
- Heating, Ventilating & Air-Conditioning
- Refrigeration
- Robotics
|
| Model
528 Specifications
|
Electrical Output Voltage
|
0 to 5 VDC, 0 to 10 VDC, 0.5 to 5.5
VDC, 1 to 5 VDC, 1 to 6 VDC, 1 to 11 VDC |
| Excitation
|
1.5 VDC Above Span to 35 VDC @ 6
mA |
| Electrical Output Current
|
4 to 20 mA |
| Loop Supply Voltage
|
24 VDC (7-35 VDC) |
Accuracy
(RSS Method)
|
±0.1% Full Scale |
| Type of Pressure
|
Gauge
Absolute*
Compound*
*Compound and absolute available on ranges up to 300 psi only. |
| Pressure Ranges
|
0 to 15, 30, 60, 100,150, 200, 300, 500, 600, 1000,
1500, 2000, 3000, 4000, 5000, 6000 psig
14.7 to 0, 15, 45, 85, 135, 185, 285 psig
1, 1.6, 2.5 4.0, 6.0, 10, 16, 25, 40, 60, 100, 160, 250, 400, 600, 690 bar |
| Thermal Effects
|
- Accuracy 0.1% Full Scale: Compensated Range °F (°C):
- -20 to +212 (-30 to +100)
- %FS/100°F(100°C)max.zero:
- 0.5 (1.0)
- %FS/100°F(100°C)max.span:
- 0.0 (1.0)
|
| Media
|
Gases or liquids compatible with 17-4PH stainless steel. (Hydrogen not recommended for use with 17-4PH stainless steel) |
Click here for data sheet:
Model 528
* Specifications subject to change without notice. If you don't see what you need here, please contact us.
|
| |
|