Heating, Ventilation, Air-Conditioning, and Refrigeration
Model 267/C267 - Very Low Differential Pressure
                                                                                 Click here for data sheet Model 267
The Model 267 with 8" static pressure probe for duct mounting. 
 

Applications

  • Heating Ventilating and Air-Conditioning (HVAC)
  • Energy Management Systems
  • Static Duct Pressure
  • Environmental Pollution Control
  • Oven Pressurization & Furnace Draft Controls
Model 267 Specifications
Electrical Output, Voltage

0 to 5 VDC
0 to 10 VDC

Bidirectional Voltage Output at Zero Mid-range of specified output
Electrical Output, Current

4 to 20 mA

Bidirectional Current Output at Zero 12 mA
Accuracy
(RSS Method)
±1.0% FS (±0.4% FS & ±0.25% FS, 
±1% FS, ±0.5% FS optional w/Cal. Cert.)
Type of Pressure Very Low Differential
Pressure Ranges
Unidirectional:
0 to 0.1, 0.25, 0.5, 1, 2.5, 5, 10, 25, 50, 100 in.WC
0 to 2.5, 5, 10, 25, 50, 100, 250 mmWC
0 to 0.25, 0.5, 1, 2.5, 5, 10, 25 mbar
0 to 25, 50, 100, 250, 500, 1000, 2500, 4000, 7000 Pa
Bi-directional:
±0.1, ±0.25, ±0.5, ±1, ±2.5,± 5, ±10, ±25, ±50 in.WC
±2.5, ±5, ±10, ±25, ±50, ±100, mmWC
±0.25, ±0.5, ±1, ±2.5, ±5, ±10 mbar
±25, ±50, ±100, ±250, ±500, ±100, 2500 Pa
Thermal Effects
Compensated Range °F (°C):
+40 to +149 (+5 to +65)
%FS/°F(°C) zero/span shift:
±0.033 (±0.06) zero and span combined
Media Typically air or similar non-conducting gases
Option LCD Display

Click here for data sheet Model 267

* Specifications subject to change without notice. If you don't see what you need here, please contact us.

   
top of page   |PREVIOUS| |INDEX| |NEXT|

|Division Profile| |Products| |Installation Instructions| |Technology|
|Application Notes| |News Releases| |Articles| |Trade Shows| |Sales Offices|

|Site Map| |About Us| |Contact Setra| |Employment|

|Home Page|

   
  159 Swanson Road, Boxborough, MA 01719-1304
Tel (978) 263-1400 · Toll Free (800) 257-3872
     
    ©1998 Setra Systems, Inc. All rights reserved. All names and logos are trademarks. All other names, logos, and trademarks are property of their respective owners.

Web site design by DreamLight Incorporated: DreamLight.com